Vacuum contactor

MEDIUM VOLTAGE VACUUM CONTACTORS and Starters

Greenstone USA vacuum contactors are used to efficiently protect and control motors, switchgear, transformers, capacitor banks and breakers for many different applications. Our vacuum contactors are widely used in the gas, petroleum, Mining and many other industries where protection is needed. Our vacuum contactors are used to replace Siemens, Toshiba and many other manufacturers.

Vacuum Contactor & Starter Ratings for voltage of 2.5KV to 7.2KV

200A 400A 600A 1200A
2.5KV VC3/200/2500 VC3/400/2500 VC3/600/2500 VC3/1200/2500
5.0KV VC3/200/5000 VC3/400/5000 VC3/600/5000 VC3/1200/5000
5.0KV VC3/200/5000 VC3/400/5000 VC3/600/5000 VC3/1200/5000
7.2KV VC3/200/7200 VC3/400/7200 VC3/600/7200 VC3/1200/7200

Vacuum Contactor power ratings

Operational rated current 200A 400A 600A 800A/1200A
Operational rated frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz
E1 interrupt rating 2.5 KV 20
MVA Equivalent to 4.62 KA
——-
MVA & KA value 5.0 KV 40
MVA Equivalent to 4.62 KA
——-
Contactor only 7.2 KV 60
MVA Equivalent to 4.81 KA
——-
E2 fuse rating 400 MVA 45.7 KA RMS ——-
MVA & KA 5.0 KV 38
R max. fuse size
Withstand KA 5.0 KV 57.8 KA -Peak ,38
R -Fuse
——-
Short time current 1Sec. KA 6 7 9 12
5Sec. KA 4 5 6 9
15Sec .KA 2 2.6 3 6
Switching frequency 300/Hr
Elec. life at rated current .6×106 .40×106 .250×106 .250×106
Mechanical life .75×106
Dielectric strength 20KV 1min
Impulse withstand B.I.L 1.2×50us
60KV
Chopping current max. .9A

Vacuum Contactor control ratings AC & DC

Rated control voltage 120/240V 50/60Hz AC 125/250VDC
Allowable fluctuation +10-15% +10-20%
Closing power VA/Duration 650 VA/45 MS 1300 VA/45 MS
Holding power 7
VA AC .47A DC
14
VA AC .924A DC
Opening time Ave. 90
MS at 60Hz
Closing time Ave. 40
MS at 60Hz
Pick up voltage Min. 102 V or less
Drop out voltage Ave. 70% or less
Recommended control trans. (AC Only) 300 VA ——- 600VA

Vacuum contactor application conditions

Standard auxiliary contact ratings Current Continuous AC/DC 10A/5A
Voltage 600V Max.-48V Min. NEMA A600 (AC) P600 (DC)
AC Make/Break 7200VA/720 VA
DC Make/Break 125/250 V 138VA 300/600V 138VA
Additional auxiliary contact relay ratings Current Continuous AC/DC 10A/2.5A
Voltage 600V Max.-48V Min. NEMA A600 (AC) Q300 (DC)
AC Make/Break 7200VA/720VA
DC Make/Break 125/250V/69VA
Weight ——- 48
lbs.
96
lbs.
Voltage KV 2.5 3.3 4.16 6.6
Motor Type Current Motor HP
.8 P.F.Ind. or syn motor 200A 900 1250 1500 2500
1.0 P.F.syn motor 200A 1000 1500 1750 2750
.8 P.F.Ind. or syn Motor 400A 1750 2250 3000 5000
1.0 P.F.syn motor 400A 2000 2500 3500 2520
.8 P.F.Ind. or syn motor 600A 2250 3250 4500 6750
1.0 P.F.syn motor 600A 2250 3500 4750 7000
.8 P.F.Ind. or syn Motor 800A 2750 4000 5500 8000

Transformer Load KVA

Three phase transformer 200A 750 1000 1500 2000
400A 1500 2000 3000 4000
600A 2500 3000 4250 6000
800A 2750 3750 5250 7500
1200A 4100 5000 7000 10000

Capacitor Load KVAR

Three phase capacitor 200A 550 750 1050 1500
400A 1125 1500 2250 3000
600A 1650 2250 3375 4500
800A 2200 2900 4500 5000
1200A 2750 3750 5625 7500

Vacuum Contactor current rating

Maximum Horsepower Ratings

Open Type

(A) .8pf Ind. Or Syn. Motor 1.0pf Syn. Motor Catalog No.

2500Volts

200 900 1000 VC3/200/2500
400 1750 2000 VC3/400/2500
600 2250 2500 VC3/600/2500
800 2750 —– VC3/800/2500
1200 —– —– VC3/1200/2500

4160Volts

200 1500 1750 VC3/200/5000
400 3000 3500 VC3/400/5000
600 4500 4750 VC3/600/5000
800 5500 —– VC3/800/5000
1200 —– —– VC3/1200/5000

6600Volts

200 2500 2750 VC3/200-7200
400 5000 5250 VC3/400-7200
600 6750 7000 VC3/600-7200
800 8000 —– VC3/800-7200
1200 —– —– VC3/1200-7200

Coil Table

Voltage AC
Suffix
Voltage DC Suffix
120 -76 125 -125
240 -26 250 -250

Control Diagram

Circuit Assembly

Dimensions

Medium Voltage Vacuum Contactor & Starter Ratings 1.5KV & 3.6KV

80/60V 160A 320A 600A 1000A
3
Pole
1.5KV VC3/160/1500 VC320/1500 VC3/600/1500 VC3/1000/1500
3.6KV VC3/160/3600 VC320/3600 VC3/600/3600 VC3/1000/3600

Power Ratings

Rated Insulating And Operational Voltage 1500/3600
Rated Operational Current 160 320 600 1000
Rated Frequency 50/400Hz
Making Current 1600 3200 6000 6000
Breaking Current 1600 3200 6000 6000
Dielectric Strength/BIL 6KV-1 min. /45KV. 1.2×50 Micro/Sec.
Interrupting Current 4400 5000 6000 6000
Withstand Current 30KA-3Hz
Short Time Current 1Sec. 5000 7000 9000 11000
2Sec. 3000 5000 7000 9000
Mechanical Life 2×106
Electrical Life At Rated Current – AC3 Duty 1×106
Switching Frequency 00/hr
Chop Current Min. .55A
Max. .9A

Control Ratings

Description 200A/400A 600A 1000A
Rated Control Voltage 120/240V 50/400Hz
Allowable Fluctuation +10% of rated -25%voltage
Closing Power VA/Duration 950VA/17MS 1900VA/17MS 2850VA/17MS
Holding Power 9VA 18VA 27VA
Opening Time Ave. 90MS at 60Hz
Closing Time Ave. 17MS at 60Hz
Picking Up Voltage 75%Ue or less
Drop Out Voltage 65%Ue or less
Recommended Control Transformer When Required 250VA When Required 500VA When Required 750VA

Application Conditions

Installation All planes up to 6600 ft.(2000m)
Ambient Storage -65℉(-54℃)+160℉(71℃)
Operating -40℉(-40℃)+135℉(67℃)
Vibration/Shock 40Hz-2G/30G
Weight 160/320A 12lbs.(5.45kg) 24lbs.(11kg) 36lbs,(16.36kg)
Dimensions (mm) 225×189×200 450×189×200 676×189×200

Motor HP

Volts 160A 320A 600A 1000A
230 60 125 200 —–
460 125 250 500 —–
1000 300 600 1200 —–
1500 420 850 1600 —–
2300 600 1250 2400 —–
3300 960 1920 3700 —–

Transformer Load (KVA)

Volts 160A 320A 600A 1000A
230 66 133 250 415
460 127 255 500 746
1000 277 554 1000 1730
1500 415 850 1500 2600
2300 665 1330 2500 4150
3300 910 1820 3400 5700

Capacitor Load(KVAR)

Volts 160A 320A 600A 1000A
230 50 100 180 310
460 95 190 360 595
1000 205 415 750 1300
1500 310 620 1125 1450
2300 500 1000 1875 3110
3300 700 1365 2550 4275

Coil Table

Voltage AC Suffix Voltage DC Suffix
120 -76 125 -125
240 -26 250 -250